Fronius official logoCEC-Listed · 240V ResidentialString

Fronius Primo 15.0-1 208-240 (15 kW)

15 kW, 240 Vac Grid Support Utility Interactive Inverter with arc detector and meter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .

Continuous AC Output
15 kW
CEC Weighted Eff.
97%
MPPT / Max DC
320–800V / 800V
NEC 705.12 Breaker
80A @ 240V
Inverter Engineering Tools
Test String Sizing With Panels →
Fronius Primo 15.0-1 208-240 — Real Fronius solar inverter installation
Real Fronius solar inverter installationWikimedia Commons — File:Bregenz-Vorarlberger Kraftwerke-Inverter Test bay-Fronius Ohmpilot 9 0-3-01ASD.jpg (CC BY-SA 4.0)
DC INPUT & MPPT TRACKING WINDOW (STRING) MPPT 320–800 Vdc 320V 800V MAX 800V PV DC INPUT ≤ 800V DC 15 kW · 97% CEC GRID-SUPPORT INVERTER AC OUTPUT 240V · 80A BRKR

Electrical & Grid-Support Datasheet

Fronius Primo 15.0-1 208-240 Electrical and Grid-Support Specifications
ManufacturerFronius
Model Number (MPN)Primo 15.0-1 208-240
Inverter TopologyString Inverter
Continuous AC Power (Paco)15 kW (15,000 W)
Nominal DC Input (Pdco)15,456 W
Nominal AC Voltage240 Vac (Split/Single-Phase)
Listed Voltage Variants208V, 240V
CEC Weighted Efficiency97%
MPPT Operating Window320 – 800 Vdc (NREL SAM Measured)
Max DC Input Voltage800 Vdc
Max DC Input Current22.7 A
Night Tare Loss0.32 W
UL 1741 Supplement SBNo / Non-US
UL 1741 Supplement SACertified
Certifying LaboratoryNot listed in CEC
Built-in Revenue MeterYes

NEC 705.12(B) Backfeed & Panel Check

NEC 705.12 Backfeed Breaker Calculation for Primo 15.0-1 208-240
Max Continuous AC Current62.5 A @ 240V
125% Continuous Duty Current78.1 A
Minimum Standard Breaker80 A
Busbar RequirementSupply-Side Tap (NEC 705.11) or 400A/Commercial Service

Recommended PV Array Pairing

Target DC/AC ratio 1.10×–1.35× (16.5–20.25 kW DC total).

Recommended Solar Panel Quantity by Wattage Class for Primo 15.0-1 208-240
Panel ClassRecommended QtyDC Array / Ratio
400W41–51 panels16.4–20.4 kW DC
440W38–46 panels16.7–20.2 kW DC
550W30–37 panels16.5–20.4 kW DC

Compatible Solar Panels for Fronius Primo 15.0-1 208-240

Test any of 3,007 panels with this inverter →
Compatible Solar Panels for Fronius Primo 15.0-1 208-240
Solar Panel ModelSTC PowerVoc (25°C)String / Pairing FitAction
Boviet Solar BVM7612M-580-H-HC-BF580 W52.42 V9–14 per string (-10°C)Verify Pair
SEG Solar SEG-580-BTA-HV580 W51.95 V9–14 per string (-10°C)Verify Pair
Qcells (Hanwha) Q.PEAK DUO XL-G11S.B3/BFG 575575 W53.5 V9–13 per string (-10°C)Verify Pair
Mission Solar MSH10-560HN4G {A}560 W50.5 V9–14 per string (-10°C)Verify Pair
Canadian Solar CS6W-555MB-AG555 W49.8 V9–14 per string (-10°C)Verify Pair
REC Solar REC475AA Pure-RX-DC475 W65.7 V7–11 per string (-10°C)Verify Pair

Engineering FAQ — Fronius Primo 15.0-1 208-240

What size circuit breaker does the Fronius Primo 15.0-1 208-240 require under NEC 705.12?
At 15 kW continuous AC output on 240V (62.5A continuous), the 125% continuous duty rule requires a minimum 80A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the Fronius Primo 15.0-1 208-240?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 15 kW unit with 16.5 kW to 20.25 kW DC of solar modules without exceeding 800V cold Voc.

More Fronius Inverters

Symo 12.0-3 208-240 (12 kW)Symo Advanced 12.0-3 208-240 (12.09 kW)Primo 12.5-1 208-240 (12.5 kW)Primo 3.8-1 208-240 (3.8 kW)Primo GEN24 3.8 208-240 SC (3.8 kW)Primo GEN24 3.8 208-240 (3.802 kW)All Fronius Equipment →