Growatt WIT 100K-HU-US (99.37 kW)
100 kW, 277 Vac Grid Support Utility Interactive Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
99.37 kW
CEC Weighted Eff.
96.5%Class Estimate
MPPT / Max DC
520–800V / 800V
NEC 705.12 Breaker
300A @ 277V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | Growatt |
|---|---|
| Model Number (MPN) | WIT 100K-HU-US |
| Inverter Topology | Commercial 3-Phase Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 99.37 kW (99,370 W) |
| Nominal DC Input (Pdco) | 102,913 W |
| Nominal AC Voltage | 277 Vac (3-Phase) |
| Listed Voltage Variants | 277V, 480V |
| CEC Weighted Efficiency | 96.5% (Class Estimate — Not listed in CEC) |
| MPPT Operating Window | 520 – 800 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 800 Vdc |
| Max DC Input Current | 155.9 A |
| Night Tare Loss | 18.36 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Intertek |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 207.1 A @ 277V |
|---|---|
| 125% Continuous Duty Current | 258.9 A |
| Minimum Standard Breaker | 300 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (109.31–134.15 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 273–335 panels | 109.2–134.0 kW DC |
| 440W | 248–305 panels | 109.1–134.2 kW DC |
| 550W | 199–244 panels | 109.5–134.2 kW DC |
CEC-Listed 240V Equivalents to Growatt WIT 100K-HU-US
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (99.37 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Compatible Solar Panels for Growatt WIT 100K-HU-US
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Boviet Solar BVM7612M-580-H-HC-BF | 580 W | 52.42 V | 14–14 per string (-10°C) | Verify Pair |
| SEG Solar SEG-580-BTA-HV | 580 W | 51.95 V | 14–14 per string (-10°C) | Verify Pair |
| Canadian Solar CS6W-520MB-AG | 520 W | 48.4 V | 15–15 per string (-10°C) | Verify Pair |
| REC Solar REC475AA Pure-RX-DC | 475 W | 65.7 V | 11–11 per string (-10°C) | Verify Pair |
| Trina Solar TSM-460NEG9RH.25 | 460 W | 36.3 V | 20–20 per string (-10°C) | Verify Pair |
| Mission Solar MSX10-445HN0B {C} | 445 W | 38.7 V | 19–19 per string (-10°C) | Verify Pair |
Engineering FAQ — Growatt WIT 100K-HU-US
What size circuit breaker does the Growatt WIT 100K-HU-US require under NEC 705.12?
At 99.37 kW continuous AC output on 277V (207.1A continuous), the 125% continuous duty rule requires a minimum 300A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the Growatt WIT 100K-HU-US?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 99.37 kW unit with 109.31 kW to 134.15 kW DC of solar modules without exceeding 800V cold Voc.