NEP (Northern Electric & Power) BDM-1200-LV (1.194 kW)
1.2 kW, 120 Vac Grid Support Utility Interactive Microinverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
1.194 kW
CEC Weighted Eff.
96.5%Class Estimate
MPPT / Max DC
22–55V / 55V
NEC 705.12 Breaker
15A @ 120V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | NEP (Northern Electric & Power) |
|---|---|
| Model Number (MPN) | BDM-1200-LV |
| Inverter Topology | Microinverter |
| Continuous AC Power (Paco) | 1.194 kW (1,194 W) |
| Nominal DC Input (Pdco) | 1,240 W |
| Nominal AC Voltage | 120 Vac (Split/Single-Phase) |
| CEC Weighted Efficiency | 96.5% (Class Estimate — Not listed in CEC) |
| MPPT Operating Window | 22 – 55 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 55 Vdc |
| Max DC Input Current | 35.4 A |
| Night Tare Loss | 13.6 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Intertek |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 9.9 A @ 120V |
|---|---|
| 125% Continuous Duty Current | 12.4 A |
| Minimum Standard Breaker | 15 A |
| Busbar Requirement | 100A Busbar (120% rule: up to 20A backfeed) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (1.31–1.61 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 1 panel | 1:1 pairing (0.34× DC/AC) |
| 440W | 1 panel | 1:1 pairing (0.37× DC/AC) |
| 550W | 1 panel | 1:1 pairing (0.46× DC/AC) |
CEC-Listed 240V Equivalents to NEP (Northern Electric & Power) BDM-1200-LV
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (1.194 kW Microinverter) and can be added directly to your US System Kit:
Engineering FAQ — NEP (Northern Electric & Power) BDM-1200-LV
What size circuit breaker does the NEP (Northern Electric & Power) BDM-1200-LV require under NEC 705.12?
At 1.194 kW continuous AC output on 120V (9.9A continuous), the 125% continuous duty rule requires a minimum 15A overcurrent breaker. Busbar note: 100A Busbar (120% rule: up to 20A backfeed).
What solar array size pairs best with the NEP (Northern Electric & Power) BDM-1200-LV?
As a 1194W microinverter, it pairs 1:1 with panels rated roughly 1254W to 1731W STC.