SMA Solar SHP FLEX-US-21 (55.076 kW)
55 kW, 208 Vac Grid Support Utility Interactive Inverter with a Nominal AC voltage range of 200 Vac - 600 Vac, and power output 50 kW - 172 kW. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
55.076 kW
CEC Weighted Eff.
97%
MPPT / Max DC
372–1195V / 1195V
NEC 705.12 Breaker
200A @ 208V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | SMA Solar |
|---|---|
| Model Number (MPN) | SHP FLEX-US-21 |
| Inverter Topology | Commercial 3-Phase Inverter |
| Continuous AC Power (Paco) | 55.076 kW (55,076 W) |
| Nominal DC Input (Pdco) | 57,216 W |
| Nominal AC Voltage | 208 Vac (3-Phase) |
| Listed Voltage Variants | 208V, 320V, 380V, 385V, 400V, 420V, 480V, 600V, 630V, 660V |
| CEC Weighted Efficiency | 97% |
| MPPT Operating Window | 372 – 1195 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 1195 Vdc |
| Max DC Input Current | 98.1 A |
| Night Tare Loss | 2.87 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | UL |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 152.9 A @ 208V |
|---|---|
| 125% Continuous Duty Current | 191.1 A |
| Minimum Standard Breaker | 200 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (60.58–74.35 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 151–186 panels | 60.4–74.4 kW DC |
| 440W | 138–169 panels | 60.7–74.4 kW DC |
| 550W | 110–135 panels | 60.5–74.3 kW DC |
CEC-Listed 240V Equivalents to SMA Solar SHP FLEX-US-21
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (55.076 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Compatible Solar Panels for SMA Solar SHP FLEX-US-21
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Boviet Solar BVM7612M-580-H-HC-BF | 580 W | 52.42 V | 10–21 per string (-10°C) | Verify Pair |
| SEG Solar SEG-580-BTA-HV | 580 W | 51.95 V | 10–21 per string (-10°C) | Verify Pair |
| Qcells (Hanwha) Q.PEAK DUO XL-G11S.B3/BFG 575 | 575 W | 53.5 V | 10–20 per string (-10°C) | Verify Pair |
| Mission Solar MSH10-560HN4G {A} | 560 W | 50.5 V | 11–21 per string (-10°C) | Verify Pair |
| Canadian Solar CS6W-555MB-AG | 555 W | 49.8 V | 11–22 per string (-10°C) | Verify Pair |
| REC Solar REC475AA Pure-RX-DC | 475 W | 65.7 V | 8–16 per string (-10°C) | Verify Pair |
Engineering FAQ — SMA Solar SHP FLEX-US-21
What size circuit breaker does the SMA Solar SHP FLEX-US-21 require under NEC 705.12?
At 55.076 kW continuous AC output on 208V (152.9A continuous), the 125% continuous duty rule requires a minimum 200A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the SMA Solar SHP FLEX-US-21?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 55.076 kW unit with 60.58 kW to 74.35 kW DC of solar modules without exceeding 1195V cold Voc.