SMA Solar STP 33-US-41 (33.3 kW)
33.3 kW, 480 Vac, 3-phase, transformerless, Grid Support Utility Interactive Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
33.3 kW
CEC Weighted Eff.
97.5%
MPPT / Max DC
330–800V / 800V
NEC 705.12 Breaker
60A @ 480V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | SMA Solar |
|---|---|
| Model Number (MPN) | STP 33-US-41 |
| Inverter Topology | Commercial 3-Phase Inverter |
| Continuous AC Power (Paco) | 33.3 kW (33,300 W) |
| Nominal DC Input (Pdco) | 34,131 W |
| Nominal AC Voltage | 480 Vac (3-Phase) |
| CEC Weighted Efficiency | 97.5% |
| MPPT Operating Window | 330 – 800 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 800 Vdc |
| Max DC Input Current | 50 A |
| Night Tare Loss | 5.43 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | UL |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 40.1 A @ 480V |
|---|---|
| 125% Continuous Duty Current | 50.1 A |
| Minimum Standard Breaker | 60 A |
| Busbar Requirement | 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (36.63–44.95 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 92–112 panels | 36.8–44.8 kW DC |
| 440W | 83–102 panels | 36.5–44.9 kW DC |
| 550W | 67–82 panels | 36.9–45.1 kW DC |
CEC-Listed 240V Equivalents to SMA Solar STP 33-US-41
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (33.3 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Compatible Solar Panels for SMA Solar STP 33-US-41
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Boviet Solar BVM7612M-580-H-HC-BF | 580 W | 52.42 V | 9–14 per string (-10°C) | Verify Pair |
| SEG Solar SEG-580-BTA-HV | 580 W | 51.95 V | 9–14 per string (-10°C) | Verify Pair |
| Qcells (Hanwha) Q.PEAK DUO XL-G11S.B3/BFG 575 | 575 W | 53.5 V | 9–13 per string (-10°C) | Verify Pair |
| Mission Solar MSH10-560HN4G {A} | 560 W | 50.5 V | 10–14 per string (-10°C) | Verify Pair |
| Canadian Solar CS6W-555MB-AG | 555 W | 49.8 V | 10–14 per string (-10°C) | Verify Pair |
| REC Solar REC475AA Pure-RX-DC | 475 W | 65.7 V | 7–11 per string (-10°C) | Verify Pair |
Engineering FAQ — SMA Solar STP 33-US-41
What size circuit breaker does the SMA Solar STP 33-US-41 require under NEC 705.12?
At 33.3 kW continuous AC output on 480V (40.1A continuous), the 125% continuous duty rule requires a minimum 60A overcurrent breaker. Busbar note: 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11).
What solar array size pairs best with the SMA Solar STP 33-US-41?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 33.3 kW unit with 36.63 kW to 44.95 kW DC of solar modules without exceeding 800V cold Voc.