SMA Solar STP 62-US-41 (62.5 kW)
62.5 kW, 480 Vac, 3-phase, transformerless, Grid Support Utility Interactive Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
62.5 kW
CEC Weighted Eff.
97.5%
MPPT / Max DC
500–800V / 800V
NEC 705.12 Breaker
100A @ 480V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | SMA Solar |
|---|---|
| Model Number (MPN) | STP 62-US-41 |
| Inverter Topology | Commercial 3-Phase Inverter |
| Continuous AC Power (Paco) | 62.5 kW (62,500 W) |
| Nominal DC Input (Pdco) | 64,326 W |
| Nominal AC Voltage | 480 Vac (3-Phase) |
| CEC Weighted Efficiency | 97.5% |
| MPPT Operating Window | 500 – 800 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 800 Vdc |
| Max DC Input Current | 88.7 A |
| Night Tare Loss | 5.43 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | UL |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 75.2 A @ 480V |
|---|---|
| 125% Continuous Duty Current | 94.0 A |
| Minimum Standard Breaker | 100 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (68.75–84.38 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 172–211 panels | 68.8–84.4 kW DC |
| 440W | 156–192 panels | 68.6–84.5 kW DC |
| 550W | 125–153 panels | 68.8–84.2 kW DC |
CEC-Listed 240V Equivalents to SMA Solar STP 62-US-41
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (62.5 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Compatible Solar Panels for SMA Solar STP 62-US-41
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Boviet Solar BVM7612M-580-H-HC-BF | 580 W | 52.42 V | 14–14 per string (-10°C) | Verify Pair |
| SEG Solar SEG-580-BTA-HV | 580 W | 51.95 V | 14–14 per string (-10°C) | Verify Pair |
| Mission Solar MSH10-560HN4G {A} | 560 W | 50.5 V | 14–14 per string (-10°C) | Verify Pair |
| Canadian Solar CS6W-555MB-AG | 555 W | 49.8 V | 14–14 per string (-10°C) | Verify Pair |
| REC Solar REC475AA Pure-RX-DC | 475 W | 65.7 V | 11–11 per string (-10°C) | Verify Pair |
| Trina Solar TSM-460NEG9RH.25 | 460 W | 36.3 V | 19–20 per string (-10°C) | Verify Pair |
Engineering FAQ — SMA Solar STP 62-US-41
What size circuit breaker does the SMA Solar STP 62-US-41 require under NEC 705.12?
At 62.5 kW continuous AC output on 480V (75.2A continuous), the 125% continuous duty rule requires a minimum 100A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the SMA Solar STP 62-US-41?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 62.5 kW unit with 68.75 kW to 84.38 kW DC of solar modules without exceeding 800V cold Voc.