SolarEdge NX13000T-US (13 kW)
13 kW, 240 Vac Grid Support Utility Interactive Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
13 kW
CEC Weighted Eff.
99%
MPPT / Max DC
370–450V / 450V
NEC 705.12 Breaker
70A @ 240V
Inverter Engineering Tools
Test String Sizing With Panels →
Electrical & Grid-Support Datasheet
| Manufacturer | SolarEdge |
|---|---|
| Model Number (MPN) | NX13000T-US |
| Inverter Topology | Hybrid Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 13 kW (13,000 W) |
| Nominal DC Input (Pdco) | 13,202 W |
| Nominal AC Voltage | 240 Vac (Split/Single-Phase) |
| Listed Voltage Variants | 208V, 240V |
| CEC Weighted Efficiency | 99% |
| MPPT Operating Window | 370 – 450 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 450 Vdc |
| Max DC Input Current | 33.4 A |
| Night Tare Loss | 5.9 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Intertek |
| Built-in Revenue Meter | Yes |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 54.2 A @ 240V |
|---|---|
| 125% Continuous Duty Current | 67.8 A |
| Minimum Standard Breaker | 70 A |
| Busbar Requirement | 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (14.3–17.55 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 36–44 panels | 14.4–17.6 kW DC |
| 440W | 33–40 panels | 14.5–17.6 kW DC |
| 550W | 26–32 panels | 14.3–17.6 kW DC |
Engineering FAQ — SolarEdge NX13000T-US
What size circuit breaker does the SolarEdge NX13000T-US require under NEC 705.12?
At 13 kW continuous AC output on 240V (54.2A continuous), the 125% continuous duty rule requires a minimum 70A overcurrent breaker. Busbar note: 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11).
What solar array size pairs best with the SolarEdge NX13000T-US?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 13 kW unit with 14.3 kW to 17.55 kW DC of solar modules without exceeding 450V cold Voc.