SolarEdge SE3800A-US (3.79 kW)
3.8 kW, 240 Vac, 1-phase Grid Support Utility Interactive PV and Battery Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
3.79 kW
CEC Weighted Eff.
98%
MPPT / Max DC
360–480V / 480V
NEC 705.12 Breaker
20A @ 240V
Inverter Engineering Tools
Test String Sizing With Panels →
Electrical & Grid-Support Datasheet
| Manufacturer | SolarEdge |
|---|---|
| Model Number (MPN) | SE3800A-US |
| Inverter Topology | Hybrid Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 3.79 kW (3,790 W) |
| Nominal DC Input (Pdco) | 3,864 W |
| Nominal AC Voltage | 240 Vac (Split/Single-Phase) |
| Listed Voltage Variants | 240V, 208V |
| CEC Weighted Efficiency | 98% |
| MPPT Operating Window | 360 – 480 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 480 Vdc |
| Max DC Input Current | 9.7 A |
| Night Tare Loss | 2.24 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | Yes |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 15.8 A @ 240V |
|---|---|
| 125% Continuous Duty Current | 19.8 A |
| Minimum Standard Breaker | 20 A |
| Busbar Requirement | 100A Busbar (120% rule: up to 20A backfeed) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (4.17–5.12 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 10–13 panels | 4.0–5.2 kW DC |
| 440W | 9–12 panels | 4.0–5.3 kW DC |
| 550W | 8–9 panels | 4.4–5.0 kW DC |
Engineering FAQ — SolarEdge SE3800A-US
What size circuit breaker does the SolarEdge SE3800A-US require under NEC 705.12?
At 3.79 kW continuous AC output on 240V (15.8A continuous), the 125% continuous duty rule requires a minimum 20A overcurrent breaker. Busbar note: 100A Busbar (120% rule: up to 20A backfeed).
What solar array size pairs best with the SolarEdge SE3800A-US?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 3.79 kW unit with 4.17 kW to 5.12 kW DC of solar modules without exceeding 480V cold Voc.