5 kW, 240 Vac, 1-phase Grid Support Utility Interactive Inverter, where x = (blank), A, or A-US. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
4.99 kW
CEC Weighted Eff.
98%
MPPT / Max DC
370–480V / 480V
NEC 705.12 Breaker
30A @ 240V
Inverter Engineering Tools
Test String Sizing With Panels →
Electrical & Grid-Support Datasheet
| Manufacturer | SolarEdge |
|---|---|
| Model Number (MPN) | SE5000x |
| Inverter Topology | String Inverter |
| Continuous AC Power (Paco) | 4.99 kW (4,990 W) |
| Nominal DC Input (Pdco) | 5,090 W |
| Nominal AC Voltage | 240 Vac (Split/Single-Phase) |
| Listed Voltage Variants | 208V, 240V |
| CEC Weighted Efficiency | 98% |
| MPPT Operating Window | 370 – 480 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 480 Vdc |
| Max DC Input Current | 12.7 A |
| Night Tare Loss | 2.24 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | Yes |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 20.8 A @ 240V |
|---|---|
| 125% Continuous Duty Current | 26.0 A |
| Minimum Standard Breaker | 30 A |
| Busbar Requirement | 200A Busbar (120% rule: up to 40A backfeed) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (5.49–6.74 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 14–17 panels | 5.6–6.8 kW DC |
| 440W | 12–15 panels | 5.3–6.6 kW DC |
| 550W | 10–12 panels | 5.5–6.6 kW DC |
Engineering FAQ — SolarEdge SE5000x
What size circuit breaker does the SolarEdge SE5000x require under NEC 705.12?
At 4.99 kW continuous AC output on 240V (20.8A continuous), the 125% continuous duty rule requires a minimum 30A overcurrent breaker. Busbar note: 200A Busbar (120% rule: up to 40A backfeed).
What solar array size pairs best with the SolarEdge SE5000x?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 4.99 kW unit with 5.49 kW to 6.74 kW DC of solar modules without exceeding 480V cold Voc.