Star Charge Americas SI125TULT10 (124.346 kW)
125 kW, 480 Vac, Bi-directional Transformerless Grid Support Utility Interactive Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
124.346 kW
CEC Weighted Eff.
99%
MPPT / Max DC
750–1050V / 1050V
NEC 705.12 Breaker
200A @ 480V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | Star Charge Americas |
|---|---|
| Model Number (MPN) | SI125TULT10 |
| Inverter Topology | Commercial 3-Phase Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 124.346 kW (124,346 W) |
| Nominal DC Input (Pdco) | 126,231 W |
| Nominal AC Voltage | 480 Vac (3-Phase) |
| CEC Weighted Efficiency | 99% |
| MPPT Operating Window | 750 – 1050 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 1050 Vdc |
| Max DC Input Current | 150.3 A |
| Night Tare Loss | 0.32 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | No |
| Certifying Laboratory | CSA Group |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 149.6 A @ 480V |
|---|---|
| 125% Continuous Duty Current | 187.0 A |
| Minimum Standard Breaker | 200 A |
| Busbar Requirement | Supply-Side Tap (NEC 705.11) or 400A/Commercial Service |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (136.78–167.87 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 342–420 panels | 136.8–168.0 kW DC |
| 440W | 311–382 panels | 136.8–168.1 kW DC |
| 550W | 249–305 panels | 136.9–167.8 kW DC |
CEC-Listed 240V Equivalents to Star Charge Americas SI125TULT10
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (124.346 kW Commercial 3-Phase Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V20.181 kW
Shenzhen Sinexcel Isuna Energy Technology · Hybrid
Isuna U20K-PH
CEC Efficiency: 97%
Engineering FAQ — Star Charge Americas SI125TULT10
What size circuit breaker does the Star Charge Americas SI125TULT10 require under NEC 705.12?
At 124.346 kW continuous AC output on 480V (149.6A continuous), the 125% continuous duty rule requires a minimum 200A overcurrent breaker. Busbar note: Supply-Side Tap (NEC 705.11) or 400A/Commercial Service.
What solar array size pairs best with the Star Charge Americas SI125TULT10?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 124.346 kW unit with 136.78 kW to 167.87 kW DC of solar modules without exceeding 1050V cold Voc.