Dyness TX11.4K-HM (11.498 kW)
11.4kW, 240Vac output,Bi-directional Transformerless Grid Support Utility Interactive Power Conversion Equipment with PCS functionality. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
11.498 kW
CEC Weighted Eff.
96.5%Class Estimate
MPPT / Max DC
200–500V / 500V
NEC 705.12 Breaker
60A @ 240V
Inverter Engineering Tools
Test String Sizing With Panels →
Electrical & Grid-Support Datasheet
| Manufacturer | Dyness |
|---|---|
| Model Number (MPN) | TX11.4K-HM |
| Inverter Topology | Hybrid Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 11.498 kW (11,498 W) |
| Nominal DC Input (Pdco) | 11,926 W |
| Nominal AC Voltage | 240 Vac (Split/Single-Phase) |
| CEC Weighted Efficiency | 96.5% (Class Estimate — Not listed in CEC) |
| MPPT Operating Window | 200 – 500 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 500 Vdc |
| Max DC Input Current | 30.6 A |
| Night Tare Loss | 0.13 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | No |
| Certifying Laboratory | CSA Group |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 47.9 A @ 240V |
|---|---|
| 125% Continuous Duty Current | 59.9 A |
| Minimum Standard Breaker | 60 A |
| Busbar Requirement | 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (12.65–15.52 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 32–39 panels | 12.8–15.6 kW DC |
| 440W | 29–35 panels | 12.8–15.4 kW DC |
| 550W | 23–28 panels | 12.7–15.4 kW DC |
Compatible Solar Panels for Dyness TX11.4K-HM
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Boviet Solar BVM7612M-580-H-HC-BF | 580 W | 52.42 V | 6–8 per string (-10°C) | Verify Pair |
| SEG Solar SEG-580-BTA-HV | 580 W | 51.95 V | 6–8 per string (-10°C) | Verify Pair |
| Qcells (Hanwha) Q.PEAK DUO XL-G11S.B3/BFG 575 | 575 W | 53.5 V | 6–8 per string (-10°C) | Verify Pair |
| Mission Solar MSH10-560HN4G {A} | 560 W | 50.5 V | 6–9 per string (-10°C) | Verify Pair |
| Canadian Solar CS6W-555MB-AG | 555 W | 49.8 V | 6–9 per string (-10°C) | Verify Pair |
| REC Solar REC475AA Pure-RX-DC | 475 W | 65.7 V | 5–7 per string (-10°C) | Verify Pair |
Engineering FAQ — Dyness TX11.4K-HM
What size circuit breaker does the Dyness TX11.4K-HM require under NEC 705.12?
At 11.498 kW continuous AC output on 240V (47.9A continuous), the 125% continuous duty rule requires a minimum 60A overcurrent breaker. Busbar note: 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11).
What solar array size pairs best with the Dyness TX11.4K-HM?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 11.498 kW unit with 12.65 kW to 15.52 kW DC of solar modules without exceeding 500V cold Voc.