SolarEdge SE10000A-US (9.94 kW)
10 kW, 240 Vac, 1-phase Grid Support Utility Interactive Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
9.94 kW
CEC Weighted Eff.
97.5%
MPPT / Max DC
360–480V / 480V
NEC 705.12 Breaker
60A @ 240V
Inverter Engineering Tools
Test String Sizing With Panels →
Electrical & Grid-Support Datasheet
| Manufacturer | SolarEdge |
|---|---|
| Model Number (MPN) | SE10000A-US |
| Inverter Topology | String Inverter |
| Continuous AC Power (Paco) | 9.94 kW (9,940 W) |
| Nominal DC Input (Pdco) | 10,205 W |
| Nominal AC Voltage | 240 Vac (Split/Single-Phase) |
| Listed Voltage Variants | 208V, 240V |
| CEC Weighted Efficiency | 97.5% |
| MPPT Operating Window | 360 – 480 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 480 Vdc |
| Max DC Input Current | 25.5 A |
| Night Tare Loss | 5.95 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | Yes |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 41.4 A @ 240V |
|---|---|
| 125% Continuous Duty Current | 51.8 A |
| Minimum Standard Breaker | 60 A |
| Busbar Requirement | 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (10.93–13.42 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 27–34 panels | 10.8–13.6 kW DC |
| 440W | 25–31 panels | 11.0–13.6 kW DC |
| 550W | 20–24 panels | 11.0–13.2 kW DC |
Engineering FAQ — SolarEdge SE10000A-US
What size circuit breaker does the SolarEdge SE10000A-US require under NEC 705.12?
At 9.94 kW continuous AC output on 240V (41.4A continuous), the 125% continuous duty rule requires a minimum 60A overcurrent breaker. Busbar note: 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11).
What solar array size pairs best with the SolarEdge SE10000A-US?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 9.94 kW unit with 10.93 kW to 13.42 kW DC of solar modules without exceeding 480V cold Voc.