Victron Energy MultiPlus-II 48/5000/70-50 (4 kW)
4 kW, 230V 50Hz Hybrid Inverter (EN-IEC 60335 / VDE-AR-N 4105 (Off-Grid/ESS)). Registry source: Manufacturer IEC Datasheet (Global Reference) · CEC listing date: · Registry snapshot: .
Continuous AC Output
4 kW
CEC Weighted Eff.
96%
MPPT / Max DC
38–66V / 66V
NEC 705.12 Breaker
25A @ 230V
Inverter Engineering Tools
Global / Non-US Reference: Designed for non-US 50Hz / 230V–400V grids; not UL 1741-SB listed for US interconnection.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | Victron Energy |
|---|---|
| Model Number (MPN) | MultiPlus-II 48/5000/70-50 |
| Inverter Topology | Hybrid Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 4 kW (4,000 W) |
| Nominal DC Input (Pdco) | 4,167 W |
| Nominal AC Voltage | 230 Vac (Split/Single-Phase) |
| CEC Weighted Efficiency | 96% |
| MPPT Operating Window | 38 – 66 Vdc (Manufacturer IEC Datasheet) |
| Max DC Input Voltage | 66 Vdc |
| Max DC Input Current | 100 A |
| Night Tare Loss | 2 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | No |
| Certifying Laboratory | EN-IEC 60335 / VDE-AR-N 4105 (Off-Grid/ESS) |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 17.4 A @ 230V |
|---|---|
| 125% Continuous Duty Current | 21.8 A |
| Minimum Standard Breaker | 25 A |
| Busbar Requirement | 200A Busbar (120% rule: up to 40A backfeed) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (4.4–5.4 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 11–14 panels | 4.4–5.6 kW DC |
| 440W | 10–12 panels | 4.4–5.3 kW DC |
| 550W | 8–10 panels | 4.4–5.5 kW DC |
CEC-Listed 240V Equivalents to Victron Energy MultiPlus-II 48/5000/70-50
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (4 kW Hybrid Inverter) and can be added directly to your US System Kit:
Engineering FAQ — Victron Energy MultiPlus-II 48/5000/70-50
What size circuit breaker does the Victron Energy MultiPlus-II 48/5000/70-50 require under NEC 705.12?
At 4 kW continuous AC output on 230V (17.4A continuous), the 125% continuous duty rule requires a minimum 25A overcurrent breaker. Busbar note: 200A Busbar (120% rule: up to 40A backfeed).
What solar array size pairs best with the Victron Energy MultiPlus-II 48/5000/70-50?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 4 kW unit with 4.4 kW to 5.4 kW DC of solar modules without exceeding 66V cold Voc.