Fortress Power EdgeOn Duo 15 Pro (11.567 kW)
11.4 kW, 240 Vac Grid Support Hybrid Utility Interactive with PCS functionality. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
11.567 kW
CEC Weighted Eff.
96.5%Class Estimate
MPPT / Max DC
120–500V / 600VEstimated MPPT — Verify Datasheet
NEC 705.12 Breaker
70A @ 240V
Inverter Engineering Tools
Test String Sizing With Panels →
Electrical & Grid-Support Datasheet
| Manufacturer | Fortress Power |
|---|---|
| Model Number (MPN) | EdgeOn Duo 15 Pro |
| Inverter Topology | Hybrid Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 11.567 kW (11,567 W) |
| Nominal DC Input (Pdco) | 11,986 W |
| Nominal AC Voltage | 240 Vac (Split/Single-Phase) |
| Listed Voltage Variants | 240V, 208V |
| CEC Weighted Efficiency | 96.5% (Class Estimate — Not listed in CEC) |
| MPPT Operating Window | 120 – 500 Vdc (Nominal Class Estimate (Verify Datasheet))Estimated MPPT — Verify Manufacturer Datasheet before string design |
| Max DC Input Voltage | 600 Vdc |
| Max DC Input Current | 36.9 A |
| Night Tare Loss | 19 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | SGS |
| Built-in Revenue Meter | Yes |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 48.2 A @ 240V |
|---|---|
| 125% Continuous Duty Current | 60.3 A |
| Minimum Standard Breaker | 70 A |
| Busbar Requirement | 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (12.72–15.62 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 32–39 panels | 12.8–15.6 kW DC |
| 440W | 29–36 panels | 12.8–15.8 kW DC |
| 550W | 23–28 panels | 12.7–15.4 kW DC |
Compatible Solar Panels for Fortress Power EdgeOn Duo 15 Pro
Test any of 3,007 panels with this inverter →Estimated MPPT — Verify Manufacturer DatasheetThis inverter’s MPPT window (120–500 Vdc) is a topology estimate because the CEC file did not list explicit MPPT bounds. Confirm exact startup and MPPT voltage limits on the manufacturer datasheet before finalizing string lengths.
| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| Boviet Solar BVM7612M-580-H-HC-BF | 580 W | 52.42 V | 4–10 per string (-10°C) | Verify Pair |
| SEG Solar SEG-580-BTA-HV | 580 W | 51.95 V | 4–10 per string (-10°C) | Verify Pair |
| Qcells (Hanwha) Q.PEAK DUO XL-G11S.B3/BFG 575 | 575 W | 53.5 V | 4–10 per string (-10°C) | Verify Pair |
| Mission Solar MSH10-560HN4G {A} | 560 W | 50.5 V | 4–10 per string (-10°C) | Verify Pair |
| Canadian Solar CS6W-555MB-AG | 555 W | 49.8 V | 4–11 per string (-10°C) | Verify Pair |
| REC Solar REC475AA Pure-RX-DC | 475 W | 65.7 V | 3–8 per string (-10°C) | Verify Pair |
Engineering FAQ — Fortress Power EdgeOn Duo 15 Pro
What size circuit breaker does the Fortress Power EdgeOn Duo 15 Pro require under NEC 705.12?
At 11.567 kW continuous AC output on 240V (48.2A continuous), the 125% continuous duty rule requires a minimum 70A overcurrent breaker. Busbar note: 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11).
What solar array size pairs best with the Fortress Power EdgeOn Duo 15 Pro?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 11.567 kW unit with 12.72 kW to 15.62 kW DC of solar modules without exceeding 600V cold Voc.