SolarEdge SE17.3KUS (16.564 kW)
17.3 kW, 208 Vac, 3-phase Grid Support Utility Interactive Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
16.564 kW
CEC Weighted Eff.
97%
MPPT / Max DC
400–600V / 600V
NEC 705.12 Breaker
60A @ 208V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | SolarEdge |
|---|---|
| Model Number (MPN) | SE17.3KUS |
| Inverter Topology | String Inverter |
| Continuous AC Power (Paco) | 16.564 kW (16,564 W) |
| Nominal DC Input (Pdco) | 17,165 W |
| Nominal AC Voltage | 208 Vac (3-Phase) |
| CEC Weighted Efficiency | 97% |
| MPPT Operating Window | 400 – 600 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 600 Vdc |
| Max DC Input Current | 37.3 A |
| Night Tare Loss | 5.28 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Intertek |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 46 A @ 208V |
|---|---|
| 125% Continuous Duty Current | 57.5 A |
| Minimum Standard Breaker | 60 A |
| Busbar Requirement | 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (18.22–22.36 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 46–56 panels | 18.4–22.4 kW DC |
| 440W | 41–51 panels | 18.0–22.4 kW DC |
| 550W | 33–41 panels | 18.1–22.6 kW DC |
CEC-Listed 240V Equivalents to SolarEdge SE17.3KUS
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (16.564 kW String Inverter) and can be added directly to your US System Kit:
Compatible Solar Panels for SolarEdge SE17.3KUS
Test any of 3,007 panels with this inverter →| Solar Panel Model | STC Power | Voc (25°C) | String / Pairing Fit | Action |
|---|---|---|---|---|
| SEG Solar SEG-450-BTD-BG | 450 W | 39.6 V | 14–14 per string (-10°C) | Verify Pair |
| Canadian Solar CS6.2-48TM-430H | 430 W | 35 V | 16–16 per string (-10°C) | Verify Pair |
| REC Solar REC430AA Pure 2 | 430 W | 49 V | 11–11 per string (-10°C) | Verify Pair |
| Qcells (Hanwha) Q.TRON BLK-G1+ 395 | 395 W | 41.51 V | 13–13 per string (-10°C) | Verify Pair |
| Silfab Solar SIL-440QD | 440 W | 38.97 V | 14–14 per string (-10°C) | Verify Pair |
Engineering FAQ — SolarEdge SE17.3KUS
What size circuit breaker does the SolarEdge SE17.3KUS require under NEC 705.12?
At 16.564 kW continuous AC output on 208V (46A continuous), the 125% continuous duty rule requires a minimum 60A overcurrent breaker. Busbar note: 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11).
What solar array size pairs best with the SolarEdge SE17.3KUS?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 16.564 kW unit with 18.22 kW to 22.36 kW DC of solar modules without exceeding 600V cold Voc.