APsystems QT2-208 (1.733 kW)
1728 VA, 208 Vac Grid Support Utility Interactive Inverter. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
1.733 kW
CEC Weighted Eff.
96%
MPPT / Max DC
34–42V / 42V
NEC 705.12 Breaker
15A @ 208V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | APsystems |
|---|---|
| Model Number (MPN) | QT2-208 |
| Inverter Topology | Microinverter |
| Continuous AC Power (Paco) | 1.733 kW (1,733 W) |
| Nominal DC Input (Pdco) | 1,813 W |
| Nominal AC Voltage | 208 Vac (3-Phase) |
| CEC Weighted Efficiency | 96% |
| MPPT Operating Window | 34 – 42 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 42 Vdc |
| Max DC Input Current | 47.7 A |
| Night Tare Loss | 0.09 W |
| UL 1741 Supplement SB | Certified (3rd Ed.) |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | CSA Group |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 4.8 A @ 208V |
|---|---|
| 125% Continuous Duty Current | 6.0 A |
| Minimum Standard Breaker | 15 A |
| Busbar Requirement | 100A Busbar (120% rule: up to 20A backfeed) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (1.91–2.34 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 1 panel | 1:1 pairing (0.23× DC/AC) |
| 440W | 1 panel | 1:1 pairing (0.25× DC/AC) |
| 550W | 1 panel | 1:1 pairing (0.32× DC/AC) |
CEC-Listed 240V Equivalents to APsystems QT2-208
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (1.733 kW Microinverter) and can be added directly to your US System Kit:
Engineering FAQ — APsystems QT2-208
What size circuit breaker does the APsystems QT2-208 require under NEC 705.12?
At 1.733 kW continuous AC output on 208V (4.8A continuous), the 125% continuous duty rule requires a minimum 15A overcurrent breaker. Busbar note: 100A Busbar (120% rule: up to 20A backfeed).
What solar array size pairs best with the APsystems QT2-208?
As a 1733W microinverter, it pairs 1:1 with panels rated roughly 1820W to 2513W STC.