Generac XVT114G03 (11.748 kW)
11.4 kW, 208 Vac Grid Support Utility Interactive Inverter with PCS Functionality. Registry source: CEC Grid-Support Inverter List (Nov 2026) · CEC listing date: · Registry snapshot: .
Continuous AC Output
11.748 kW
CEC Weighted Eff.
97%
MPPT / Max DC
390–420V / 420V
NEC 705.12 Breaker
45A @ 208V
Inverter Engineering Tools
CEC-Listed · Commercial / C&I: Commercial / legacy unit — see US residential split-phase equivalents below.
View US 240V Equivalents →Run String Voltage Check →
Electrical & Grid-Support Datasheet
| Manufacturer | Generac |
|---|---|
| Model Number (MPN) | XVT114G03 |
| Inverter Topology | Hybrid Inverter (PV + Battery Hybrid) |
| Continuous AC Power (Paco) | 11.748 kW (11,748 W) |
| Nominal DC Input (Pdco) | 12,088 W |
| Nominal AC Voltage | 208 Vac (3-Phase) |
| CEC Weighted Efficiency | 97% |
| MPPT Operating Window | 390 – 420 Vdc (NREL SAM Measured) |
| Max DC Input Voltage | 420 Vdc |
| Max DC Input Current | 30.2 A |
| Night Tare Loss | 0.13 W |
| UL 1741 Supplement SB | No / Non-US |
| UL 1741 Supplement SA | Certified |
| Certifying Laboratory | Not listed in CEC |
| Built-in Revenue Meter | No / Optional |
NEC 705.12(B) Backfeed & Panel Check
| Max Continuous AC Current | 32.6 A @ 208V |
|---|---|
| 125% Continuous Duty Current | 40.8 A |
| Minimum Standard Breaker | 45 A |
| Busbar Requirement | 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11) |
Recommended PV Array Pairing
Target DC/AC ratio 1.10×–1.35× (12.92–15.86 kW DC total).
| Panel Class | Recommended Qty | DC Array / Ratio |
|---|---|---|
| 400W | 32–40 panels | 12.8–16.0 kW DC |
| 440W | 29–36 panels | 12.8–15.8 kW DC |
| 550W | 23–29 panels | 12.7–15.9 kW DC |
CEC-Listed 240V Equivalents to Generac XVT114G03
Installing in the United States? These UL 1741-SB / 240V split-phase inverters match this class (11.748 kW Hybrid Inverter) and can be added directly to your US System Kit:
CEC-Listed · 240V11.589 kW
General Motors Energy · Hybrid
GM Energy Inverter e1.11
CEC Efficiency: 97.5%
Engineering FAQ — Generac XVT114G03
What size circuit breaker does the Generac XVT114G03 require under NEC 705.12?
At 11.748 kW continuous AC output on 208V (32.6A continuous), the 125% continuous duty rule requires a minimum 45A overcurrent breaker. Busbar note: 200A Busbar + 175A Main Derate OR Supply-Side Tap (NEC 705.11).
What solar array size pairs best with the Generac XVT114G03?
For balanced annual yield (1.10× to 1.35× DC/AC ratio), pair this 11.748 kW unit with 12.92 kW to 15.86 kW DC of solar modules without exceeding 420V cold Voc.